Key Features
- Low cost, compact remote IO Modules.
- 24 VDC powered.
- DIN rail mounting.
- LEDs for all digital IO, power, and communications.
FIOA 0402 U is Analog Input Output Model having 4 Universal Analog inputs and 2 Analog outputs. The Analog inputs can be Voltage (0-10V, 1-5V), Current (0–20 mA, 4–20 mA), mV
(0–100 mV, 0–50 mV), RTD ( PT 100 Alpha1 and Alpha2 constant), Thermocouple ( B,R,S,E,J,K,N,T ).
Each input channel can be configured independently to work as any of the above type as per configuration made in the PRIZM software. The Analog outputs can be Voltage (0–10 V) or Current (4–20 mA). Output channels also are software configurable to current or voltage. Unit supports standard Modbus RTU (slave) protocol for communicating with master device.
Analog inputs and outputs are isolated from the communication port. The power supply is isolated from all internal circuitry. Input and Output channels of the FIOA are user configurable and any combination of input types is possible. Prizm Setup Software helps the user to configure the FIOA units and use them as per his requirements.
Model Series
- FIOA-0402-U-B
- FIOA-0402-U-16-B
- FIOA-0800-L-B
- FIOA-0800-R-B
- FIOA-0800-RP-B
- FIOD-0008-R-B
- FIOD-0016-C-B
- FIOD-0016-P-B
- FIOD-0016-R-B
- FIOD-0404-C-B
- FIOD-0404-P-B
- FIOD-0404-R-B
- FIOD-0808-C-B
- FIOD-0808-P-B
- FIOD-0808-R-B
- FIOD-1600-B
- FIOD-EN-0404C
General Specifications | |
Power | + 24V DC ± 10%, 4W maximum |
Operating Temp. | 0º to 50º C |
Storage Temp. | -20º to 80º C |
Humidity | 10% to 90% (Non Condensing) |
Mounting | DIN rail or back panel mounting |
Dimensions | 100 W x 70 H x 35 D mm |
Immunity to ESD | as per IEC61000-4-2 |
Immunity to Fast Transients | as per IEC61000-4-4 |
Immunity to Radiated electromagnetic field | as per IEC61000-4-3 |
Immunity to Conducted disturbances | as per IEC61000-4-6 |
Surge | as per IEC61000-4-5 |
Radiated emission | as per EN61000-6-4 |
Communication Port | 2 wire RS485, RS232,CMOS logic Signals are available on RJ45 comm port. Same two wire RS485 signals are provided on terminal block |
Driver | Modbus RTU Slave |
Baud rate | 9600, 19.2k, 57.6k or 115.2k (software configurable) |
Parity | Odd, Even or None (software configurable) |
Device ID | 1-255 (Software configurable) |
Isolation | 1.5KV isolation between communication ports, I/O and power supply section. |